CVE-2022-0369 is a high severity directory traversal flaw in the Restore Workspace feature of Triangle MicroWorks SCADA Data Gateway, scored 8.8 by NVD. It can lead to code execution as SYSTEM. The Zero Day Initiative advisory says it is fixed in version 5.01.02, so upgrade to that or later.
What's affected
The record says the flaw sits in the Restore Workspace feature. A user supplied path is not validated before being used in file operations, which lets a remote attacker execute code in the context of SYSTEM. Authentication is required, but the record says the existing authentication mechanism can be bypassed.
ZDI advisory ZDI-23-450, published on April 14th 2023, says the issue is fixed in version 5.01.02. It was reported to the vendor on 2022-05-09 and released after coordinated disclosure on 2023-04-14.
The sources disagree on severity. NVD scores the record 8.8 High with the vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H. ZDI scores it 7.2, with a vector that needs high privileges. The difference is how each treats the authentication step. Plan on the higher score unless you have confirmed that nobody untrusted can reach the gateway.
Weakness class: CWE-22.
How to check if you're exposed
Open the SCADA Data Gateway application and read its version from the About screen or the installed programs list on the host. Anything before 5.01.02 is in range.
Check where the gateway listens. Industrial gateways often sit on a network segment shared with devices that were never meant to face outside users, and the record's note about bypassable authentication means access control by login alone is not enough.
Find any scripts or runbooks that use the Restore Workspace function, since that is the feature at risk, and note who is allowed to use it.
What to do now
- Find every Triangle MicroWorks SCADA Data Gateway host and its version.
- Upgrade to 5.01.02 or later.
- Restrict network access to the gateway to the engineering hosts that need it.
- Limit who can use Restore Workspace, and restore only workspace files you created.
- Check the gateway host for unexpected files, after the upgrade.
Why it matters
Directory traversal means a path that came from outside is used as is. If it contains parent directory references, the file operation can reach folders far from the intended one. Writing a file to a location that the service later loads is a short step to running code, and the record notes the code would run as SYSTEM, the highest local privilege on Windows. It files the issue as CWE-22.
Gateways in industrial settings translate between protocols such as DNP3 and IEC 60870 and the systems that monitor a grid or plant. They hold connections to many devices, so a compromised gateway is a good place to watch and tamper with traffic.
The disclosure timeline is also instructive. More than eleven months passed between the report to the vendor and the public advisory. Operators of industrial software should assume fixes arrive quietly and read advisories from independent sources such as ZDI.
This CVE is not listed in the CISA Known Exploited Vulnerabilities catalog, and none of the pages I read state that it is exploited in the wild. That is a statement about what is known, not a reason to delay the fix.
Quick check
Which version fixes CVE-2022-0369?
The ZDI advisory says the issue is fixed in version 5.01.02.
Does it need a login?
The record says authentication is required but that the existing authentication mechanism can be bypassed.
Sources
Last reviewed: 19 October 2026.