CVE-2025-3941 is a medium severity flaw (CVSS 5.4) in Tridium Niagara Framework and Enterprise Security on Windows, caused by improper handling of the Windows ::DATA alternate data stream. Releases before 4.14.2, 4.15.1 and 4.10.11 are affected. Tridium recommends 4.14.2u2, 4.15u1 or 4.10u11, so plan the upgrade.
What's affected
The record names Tridium Niagara Framework and Niagara Enterprise Security on Windows. Affected versions are before 4.14.2, before 4.15.1 and before 4.10.11, so three supported release lines are covered. The description says the flaw allows input data manipulation, through improper handling of the Windows ::DATA alternate data stream.
Tridium recommends upgrading to Niagara Framework and Enterprise Security versions 4.14.2u2, 4.15u1 or 4.10u11. The record writes the last two with slightly different punctuation, so confirm the exact build names in Tridium's bulletin.
The record lists the weakness as CWE-69 (improper handling of Windows ::DATA alternate data streams) and CWE-706 (use of an incorrectly resolved name or reference). The CVSS 3.1 score is 5.4 (medium), with the vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:N. The vector shows the flaw can be reached over the network, and a low privilege account is needed. Confidentiality impact is rated low, integrity low and availability no.
The record does not say this flaw is exploited in the wild, and the CISA Known Exploited Vulnerabilities flag is false.
How to check if you're exposed
Niagara is an industrial and building automation platform, so the checks are about inventory and version.
- Find the Niagara version on each system. Open the product's version or about information in Workbench, or in the station's platform details, and note the release line (4.10, 4.14 or 4.15) and the update level.
- Compare it with the fixed builds in the record: 4.14.2u2, 4.15u1 and 4.10u11. Anything older than the fixed build in its line needs the update.
- Check which Niagara hosts run Windows. This CVE names Windows only.
- Open the Tridium and Honeywell security notices listed in the record, and check the technical bulletin for this CVE for any extra steps.
Niagara is a vendor product, not a package you install from a registry, so a dependency scan will not show it. The Gold directory lets you look up other CVEs by product, and your asset inventory is the right place to track Niagara versions.
What to do now
- Plan the upgrade to the fixed build for your release line: 4.14.2u2, 4.15u1 or 4.10u11. Confirm the exact names in Tridium's bulletin.
- Take a backup of each station and its configuration before you upgrade, and test on a non production system if you have one.
- Keep Niagara systems off the public internet. Place them in a segmented network, reachable only through a VPN or a managed gateway.
- Review which accounts and services can reach the platform, and remove anything that is not needed.
- Inventory every Niagara system, including the operating system it runs on, so that you can tell which of the related CVEs apply to each.
- Subscribe to Tridium and Honeywell security notices so the next bulletin reaches you quickly.
Why it matters
The record lists CWE-69, improper handling of Windows ::DATA alternate data streams, and CWE-706, use of an incorrectly resolved name or reference. On NTFS, a file can carry extra named streams, and a path with a stream suffix can resolve differently from the plain file name. Code that checks names without allowing for this can be misled about which resource is being touched.
The vector shows the flaw is reachable over the network with a low privilege account, with a low impact on confidentiality and integrity. Platform specific quirks like this are easy to miss in testing on other systems. The record gives no more detail, so use the vendor bulletin for specifics.
Quick check
Which versions fix CVE-2025-3941?
The record says versions before 4.14.2, 4.15.1 and 4.10.11 are affected and recommends 4.14.2u2, 4.15u1 or 4.10u11. Confirm the names in Tridium's bulletin.
Does it affect Linux or QNX?
This entry names Windows only, because alternate data streams are a Windows file system feature.
Sources
- Gold entry for CVE-2025-3941
- NVD record for CVE-2025-3941, published 2025-05-22, as summarized above
- Honeywell product security notices, listed in the record
- Niagara Community technical bulletins, listed in the record
Last reviewed: 18 October 2026.