CVE-2023-27975: High Credential Exposure in EcoStruxure Control Expert

CVE-2023-27975 lets a local user expose protected project file access in Schneider EcoStruxure Control Expert. Update to v16.0 per the vendor notice.

Safeguard Security Team
3 min read

CVE-2023-27975 is an insufficiently protected credentials flaw in Schneider Electric EcoStruxure Control Expert. A local user who tampers with workstation memory could gain access to the project file. NVD and Schneider score it 7.1, High. The vendor lists Control Expert v16.0 as the fix.

What's affected

Schneider's notice SEVD-2024-044-01 is a shared bulletin that covers several CVEs and products. For this CVE, the relevant rows are:

  • EcoStruxure Control Expert, versions before v16.0. Fixed in v16.0.
  • EcoStruxure Process Expert, versions before v2023. The notice points to Control Expert 15.3 HF008 for the fix.

The same notice lists Modicon M340 and M580 controller firmware for other CVEs, so read its table for your exact products. Schneider gives a CVSS 3.1 score of 7.1 and a CVSS 4.0 score of 7.2, both High. NVD matches at 7.1.

How to check if you're exposed

On an engineering workstation, open the About dialog in Control Expert to read the version. For Process Expert, check the installed version and the Control Expert component it ships with. Compare with the fixed versions above.

Also list who can log on to each engineering workstation, and whether project files are kept on shared drives. The attack needs local access, so physical and remote desktop access to those machines is where to look.

What to do now

  1. Install EcoStruxure Control Expert v16.0, or the listed fix for Process Expert, and reboot the computer afterwards as the notice instructs.
  2. Restrict logons to engineering workstations to the engineers who need them.
  3. Protect project files with file permissions and keep copies off shared locations.
  4. Follow Schneider's general cybersecurity recommendations in the notice for your plant network.
  5. Check the Gold page for this CVE for later changes.

Why it matters

The weakness class is CWE-522 (Insufficiently Protected Credentials). Sensitive material, in this case what protects a project file, is stored or held in a way that someone with local access can reach. The record says tampering with workstation memory is the route.

Industrial project files describe how a plant is controlled, and some are protected with an application password. Anyone who gets around that protection learns logic they could use later. The score is not extreme, but engineering workstations are a small and valuable target, so keep them patched and tightly controlled.

Industrial change control is slower than office IT, and engineering software is often pinned to a version that matches the plant. Plan the move to v16.0 with the people who own the project files, test with a copy, and keep the old installer until you have confirmed that projects open correctly.

If you cannot update yet, the notice's general guidance still applies. Keep engineering workstations on a segmented network, restrict who can use them, and do not leave them logged in and unattended. These steps reduce the chance of a local attacker getting close enough to try.

Quick check

Does this flaw let someone attack a PLC directly?

Not by itself. The record describes access to the project file on the engineering workstation, and it needs local access to that machine.

Sources

Last reviewed: 19 October 2026.

Never miss an update

Weekly insights on software supply chain security, delivered to your inbox.

We email you a link to confirm, and only then add you to the list. Unsubscribe in one click. Privacy

Self-healing security runs on Safeguard.

Your first fix PR is minutes away.

No sales call required, even your agent can complete the purchase over MCP.